Wisconsin · investor-owned utility
Madison Gas and Electric (MGE): power factor rules
Ordinary commercial and industrial customers have no power-factor charge. One transmission-voltage interruptible schedule adjusts billed demand if low power factor isn't corrected after notice.
Power-factor rule confirmed Tariffs checked 2026-10-03
Smaller customers
Cg-2, Cg-4, Cg-5 and Cg-6 have no power-factor billing provision. MGE's service rules do set power-factor requirements for some equipment, such as motors over 100 hp.
The power-factor rule
Cp-1 C&I High Load Factor Direct Control Interruptible Service for Transmission Voltage
Applies to: Service at 69 kV or higher, interruptible demand above 10,000 kW, annual load factor of at least 90%.
How it works: After written notice, if corrective equipment isn't installed within 240 days, on-peak billed demand is scaled by 85% divided by the actual power factor.
Formula: Billed on-peak kW = registered on-peak kW × (0.85 / actual PF).
"the measured on-peak kW demands used for billing purposes thereafter will be determined by multiplying the registered on-peak demand in kW by the ratio: 85 percent/actual power factor."
Source: Madison Gas and Electric Company – Electric Rates and Rules, Electric Volume 4, Schedule Cp-1, Sheet E-4.6.1, Determination of Demand item 3. Sheet E-4.6.1 effective January 1, 2021. Checked 2026-10-03; review by 2027-10-03.
What to do next
- Size the kVAR for your load.
- Send us a bill and we'll tell you what you're paying and what correction is worth.